Cutler Hammer, Eaton & Westinghouse Breaker Frame Types
Up to 800A Cutler-Hammer, Eaton & Westinghouse
*This chart is for reference ONLY. See specific item and manufacturer for accurate specs on specific items.
| Frame | Dims (WxHxD)** | Amperage | Interrupting Rating |
| GHC | 3" x 5" x 3" | 15A - 100A | 65kA @ 240V, 14kA @ 480V |
| GD | 65kA @ 240V, 22kA @ 480V | ||
| EG | 3" x 5" x 3" | 15A - 100A | 65kA @ 240V, 22kA @ 480V |
| EHD | 4" x 6" x 3.5" | 10A - 100A | 18kA @ 240, 14kA @ 480V |
| ED | 4" x 6" x 3.5" | 15A - 225A | 65kA @ 240V |
| EDH | 4" x 6" x 3.5" | 100A - 225A | 18kA @ 240V, 14kA @ 480V |
| EDC | 200kA @ 240V, 100kA @ 480V | ||
| FDB | 4" x 6" x 3.5" | 10A - 225A | 18kA @ 240V, 14kA @ 480V, 14kA @ 600V |
| FD | 65kA @ 240V, 25kA @ 480V, 18kA @ 600V | ||
| HFD | 4" x 6" x 3.5" | 15A - 225A | 100kA @ 240V, 65kA @ 480V, 25kA @ 600V |
| FDC | 200kA @ 240V, 100kA @ 480V, 35kA @ 600V | ||
| JD | 4" x 10" x 4" | 70A - 250A | 65kA @ 240V, 25kA @ 480V, 18kA @ 600V |
| HJD | 100kA @ 240V, 65kA @ 480V, 25kA @ 600V | ||
| JDC | 200kA @ 240V, 100kA @ 480V, 35kA @ 600V | ||
| JDB | 65kA @ 240V, 25kA @ 480V, 18kA @ 600V | ||
| JG | 4" x 10" x 4" | 175A - 250A | - |
| KDB | 5.5" x 10" x 4" | 100A - 400A | 65kA @ 240V, 35kA @ 480V, 25kA @ 600V |
| KD | 65kA @ 240V, 35kA @ 480V, 25kA @ 600V | ||
| HKD | 100kA @ 240V, 65kA @ 480V, 65kA @ 600V | ||
| KDC | 200kA @ 240V, 100kA @ 480V, 50kA @ 600V | ||
| DK | 5.5" x 10" x 4" | 250A - 400A | 65kA @ 240V |
| LDB | 8.25" x 10.75" x 4" | 300A - 600A | 65kA @ 240V, 35kA @ 480V, 25kA @ 600V |
| LD | 8.25" x 10.75" x 4" | 125A - 600A | 65kA @ 240V, 35kA @ 480V, 25kA @ 600V |
| HLD | 100kA @ 240V, 65kA @ 480V, 35kA @ 600V | ||
| LG | 8.25" x 10.75" x 4" | 450A - 600A | 18kA @ 240V, 14kA @ 480V, 10kA @ 600V |
| MDL | 8.25" x 16" x 4" | 300A - 800A | 42kA @ 240V, 35kA @ 480V, 22kA @ 600V |
| HMLD | 100kA @ 240V, 65kA @ 480V, 35kA @ 600V |
**Measurements are for 3-Pole Breakers not including the handle
Cutler-Hammer, Eaton & Westinghouse
*This chart is for reference ONLY. See specific item and manufacturer for accurate specs on .
| Amperage | Dims (WxHxD)* |
| 3A - 150A | 4" x 6" x 3.5" |
| 250A - 400A | 4" x 10" x 4" |
| 400A | 5.5" x 10" x 4" |
| 600A | 8.25" x 10.75" x 4" |
| 800A - 1200A | 8.25" x 16" x 5.5" |
For more frame attributes please see the following table.
**Measurements are for 3-Pole Breakers not including the handle
Cutler-Hammer, Eaton & Westinghouse
*This chart is for reference ONLY. See specific item and manufacturer for accurate specs on specific items.
| Frame | Dims (WxHxD)** | Amperage | Interrupting Rating |
| ND | 8.25" x 16" x 5.5" | 800A - 1200A | 65kA @ 240V, 50kA @ 480V, 25kA @ 600V |
| HND | 100kA @ 240V, 65kA @ 480V, 35kA @ 600V | ||
| NDC | 200kA @ 240V, 100kA @ 480V, 50kA @ 600V | ||
| NG | 18kA @ 240V, 14kA @ 480V, 10kA @ 600V |
**Measurements are for 3-Pole Breakers not including the handle